Hi All,
I am a beginner in HVDC simulation.
I want to simulate soft start-up of an AC passive network (long subsea cable). Where in the HVDC MMC model can we adjust/modify to have voltage ramp-up.?
Thanks in advance
Regards
Dear AGUNG_OWT,You should go
Dear AGUNG_OWT,
You should go inside the MMC station model and modify the reference "Vref" used for VF-control type.
For MMC model example provided in EMPT 2.5, the path for this bloc is: VSC_1/Upper_Level_Ctrl2/VF_control
You should replace the constant bloc named "Vref" with a signal generator. Then configure this later with the appropriate ramp desired.
Note that Vref value is in pu.
Best regards,
Dear Mr SaadThank you very
Dear Mr Saad
Thank you very much for the advice
I will try it.